One Stop Telecom Power Solutions

ETP48200-C5B6 Embedded power system

Short Description:

The embedded DC power system of etp48200-c5b6 realizes the conversion of AC input to stable 48V DC output, and can be configured with four 48V / 50A rectifier modules, with the maximum output current of 200A. Each functional unit adopts standardized size design, supports hot plug, system height 5u, supports standard 19 inch rack or embedded cabinet and other installation methods. The system can adapt to a wide range of AC input, with intelligent battery management, remote monitoring and other functions.


Product Detail

Product Tags

 ETP48200-C5B6

ETP48200-C5B6 Embedded power system

Characteristic

1. 1U rectifier module: high density (42.7w / inch3), high efficiency (> 96%), reliable output at high temperature (no derating below 55 ℃).
2. Wide working temperature range of power supply: - 40 ~ + 65 ℃.
3. The power module supports hot plug, which is convenient for installation and maintenance.
4. Standard installation structure design, strong universality.
5. Compact power structure, space saving and installation cost saving.
6. Perfect module sleep function to further improve system efficiency.
7. Intelligent battery management and battery protection to extend battery life.
8. It supports environmental monitoring and can realize remote control through dry contact, serial port or network interface administration.

Application scenario

Wireless base station
Transport network
Enterprise communication network

Parameter

Product type ETP48200-C5B6
System Dimensions (w × D × h) 482.6 mm × 330 mm × 219.5 mm
Weight ≤ 20 kg(Without rectifier module)
Temperature control mode Natural heat dissipation
Installation mode 19 inch rack or embedded cabinet installation
Line mode Go up and go out
Maintenance mode Pre maintenance
Protection level IP20
AC power distribution Input system 220 / 380 VAC three phase, 220 VAC single phase compatible
Input voltage 85–300 Vac,Rated voltage:220 Vac
Frequency 45–66 Hz,Rated frequency:50/60 Hz
Input empty 1 × 63 A/3P
Lightning protection 20/40 kA,8/20 μs
AC output -
DC distribution Output voltage 42–58 Vdc,Rated voltage:53.5 Vdc
Maximum capacity 12 kW
Battery Input 2 × 125 A/1P
Load power down 1 × 80 A/1P,6 × 32 A/1P
Battery power down 1 × 80 A/1P,2 × 32 A/1P,1 × 10 A/1P
Lightning protection 10/20 kA,8/20 μs
Rectifier module Type R4850G2
Rated power 3000 W (176–300 Vac)
Dimensions (w × D × h) 105 mm × 281 mm × 40.8 mm
Efficiency > 96%
Monitoring module Type SMU06C2
Communication port RS232, RS485
Environmental Science Working temperature –40℃ ~ +65℃
(If it is used at an altitude of 3000-4000 meters, the maximum operating temperature will decrease by 1 ℃ for every 200 meters of increase)
Storage temperature –40% ~ +70%
Storage temperature relative humidity 5% – 95%(No condensation)
Height 0 – 4000 m